Experimental study on the pressure drop characteristics of steam-water two-phase flow at a low mass velocity in a four-head rifled tube
发表时间:2019-03-12 点击次数:
论文类型:期刊论文
第一作者:Zhu, Xiaojing
通讯作者:Zhu, XJ (reprint author), Dalian Univ Technol, Minist Educ, Key Lab Ocean Energy Utilizat & Energy Conservat, Dalian 116024, Peoples R China.
合写作者:Yang, Zhuqiang,Bi, Qincheng
发表时间:2017-07-25
发表刊物:APPLIED THERMAL ENGINEERING
收录刊物:SCIE、EI、Scopus
文献类型:J
卷号:122
页面范围:148-157
ISSN号:1359-4311
关键字:Rifled tube; Steam-water two-phase flow; Pressure drop characteristic; Self-compensating; Low mass velocity
摘要:The pressure drop characteristics of steam-water two-phase flow at a low mass velocity in a four-head rifled tube were experimentally studied under an adiabatic condition with pressure ranging from 11.3 to 21.5 MPa, mass velocity ranging from 250 to 1200 kg/m(2) s, and steam quality ranging from 0 to 1. A test section composed of a 2000 mm long horizontal tube and 3500 mm long vertical tube was set up to fully evaluate the pressure drop characteristics, including the gravitational pressure drop and frictional pressure drop. It was found that the self-compensating characteristic is present in the four-head rifled tube when the mass velocity is lower than a certain critical value. The major parameters affecting the two-phase multiplier are pressure and steam quality. The two-phase multiplier increases with increasing steam quality and decreases with increasing pressure. In the near-critical pressure region, the two-phase frictional pressure drop approaches that of single phase flow because the density difference between water and steam is small. A new correlation for the two-phase multiplier for the frictional pressure drop of steam-water two-phase flow in the four-head rifled tube was proposed based on a total of 516 experimental data points, with a root mean square error of less than 20%. Comparing these results with previous correlations, the two-phase frictional pressure drop in the rifled tube is lower than those studied by previous scholars under low-velocity conditions, especially in the high steam quality region. The results provide instructive guidelines to improve the design and operational safety of a supercritical circulating fluidized bed boiler. (C) 2017 Elsevier Ltd. All rights reserved.
是否译文: